Pages


Equivalent Lengths of Valves and Fittings in Pipeline Pressure Drop Calculations

One of the most basic calculations performed by any process engineer, whether in design or in the plant, is line sizing and pipeline pressure loss. Typically known are the flow rate, temperature and corresponding viscosity and specific gravity of the fluid that will flow through the pipe. These properties are entered into a computer program or spreadsheet along with some pipe physical data (pipe schedule and roughness factor) and out pops a series of line sizes with associated Reynolds Number, velocity, friction factor and pressure drop per linear dimension. The pipe size is then selected based on a compromise between the velocity and the pressure drop. With the line now sized and the pressure drop per linear dimension determined, the pressure loss from the inlet to the outlet of the pipe can be calculated
Calculating Pressure Drop
The most commonly used equation for determining pressure drop in a straight pipe is the Darcy Weisbach equation. One common form of the equation which gives pressure drop in terms of feet of head is given below:
ives pressure drop in terms of feet of head is given below:
The term
is commonly referred to as the Velocity Head.
Another common form of the Darcy Weisbach equation that is most often used by engineers because it gives pressure drop in units of pounds per square inch (psi) is:

To obtain pressure drop in units of psi/100 ft, the value of 100 replaces L in Equation 2.
The total pressure drop in the pipe is typically calculated using these five steps. (1) Determine the total length of all horizontal and vertical straight pipe runs. (2) Determine the number of valves and fittings in the pipe. For example, there may be two gate valves, a 90o elbow and a flow thru tee. (3) Determine the means of incorporating the valves and fittings into the Darcy equation. To accomplish this, most engineers use a table of equivalent lengths. This table lists the valve and fitting and an associated length of straight pipe of the same diameter, which will incur the same pressure loss as that valve or fitting. For example, if a 2” 90o elbow were to produce a pressure drop of 1 psi, the equivalent length would be a length of 2” straight pipe that would also give a pressure drop of 1 psi. The engineer then multiplies the quantity of each type of valve and fitting by its respective equivalent length and adds them together. (4) The total equivalent length is usually added to the total straight pipe length obtained in step one to give a total pipe equivalent length. (5) This total pipe equivalent length is then substituted for L in Equation 2 to obtain the pressure drop in the pipe.
See any problems with this method?
Relationship Between K, Equivalent Length and Friction Factor
The following discussion is based on concepts found in reference 1, the CRANE Technical Paper No. 410. It is the author’s opinion that this manual is the closest thing the industry has to a standard on performing various piping calculations. If the reader currently does not own this manual, it is highly recommended that it be obtained.
As in straight pipe, velocity increases through valves and fittings at the expense of head loss. This can be expressed by another form of the Darcy equation similar to Equation 1:

When comparing Equations 1 and 3, it becomes apparent that:

K is called the resistance coefficient and is defined as the number of velocity heads lost due to the valve or fitting. It is a measure of the following pressure losses in a valve or fitting:
  • Pipe friction in the inlet and outlet straight portions of the valve or fitting
  • Changes in direction of flow path
  • Obstructions in the flow path
  • Sudden or gradual changes in the cross-section and shape of the flow path
Pipe friction in the inlet and outlet straight portions of the valve or fitting is very small when compared to the other three. Since friction factor and Reynolds Number are mainly related to pipe friction, K can be considered to be independent of both friction factor and Reynolds Number. Therefore, K is treated as a constant for any given valve or fitting under all flow conditions, including laminar flow. Indeed, experiments showed1 that for a given valve or fitting type, the tendency is for K to vary only with valve or fitting size. Note that this is also true for the friction factor in straight clean commercial steel pipe as long as flow conditions are in the fully developed turbulent zone. It was also found that the ratio L/D tends towards a constant for all sizes of a given valve or fitting type at the same flow conditions. The ratio L/D is defined as the equivalent length of the valve or fitting in pipe diameters and L is the equivalent length itself.
In Equation 4, ¦ therefore varies only with valve and fitting size and is independent of Reynolds Number. This only occurs if the fluid flow is in the zone of complete turbulence (see the Moody Chart in reference 1 or in any textbook on fluid flow). Consequently, ¦ in Equation 4 is not the same ¦ as in the Darcy equation for straight pipe, which is a function of Reynolds Number. For valves and fittings, ¦ is the friction factor in the zone of complete turbulence and is designated ¦t, and the equivalent length of the valve or fitting is designated Leq. Equation 4 should now read (with D being the diameter of the valve or fitting):

The equivalent length, Leq, is related to ¦t, not ¦, the friction factor of the flowing fluid in the pipe. Going back to step four in our five step procedure for calculating the total pressure drop in the pipe, adding the equivalent length to the straight pipe length for use in Equation 1 is fundamentally wrong.
Calculating Pressure Drop, The Correct Way
So how should we use equivalent lengths to get the pressure drop contribution of the valve or fitting? A form of Equation 1 can be used if we substitute ¦t for ¦ and Leq for L (with d being the diameter of the valve or fitting):

The pressure drop for the valves and fittings is then added to the pressure drop for the straight pipe to give the total pipe pressure drop.
Another approach would be to use the K values of the individual valves and fittings. The quantity of each type of valve and fitting is multiplied by its respective K value and added together to obtain a total K. This total K is then substituted into the following equation:

Notice that use of equivalent length and friction factor in the pressure drop equation is eliminated, although both are still required to calculate the values of K1. As a matter of fact, there is nothing stopping the engineer from converting the straight pipe length into a K value and adding this to the K values for the valves and fittings before using Equation 7. This is accomplished by using Equation 4, where D is the pipe diameter and ¦ is the pipeline friction factor.
How significant is the error caused by mismatching friction factors? The answer is, it depends. Below is a real world example showing the difference between the Equivalent Length method (as applied by most engineers) and the K value method to calculate pressure drop.
An Example
The fluid being pumped is 94% Sulfuric Acid through a 3”, Schedule 40, Carbon Steel pipe:
Mass Flow Rate, lb/hr:
63,143
Volumetric Flow Rate, gpm:
70
Density, lb/ft3:
112.47
S.G.
1.802
Viscosity, cp:
10
Temperature, oF:
127
Pipe ID, in:
3.068
Velocity, fps:
3.04
Reynold's No:
12,998
Darcy Friction Factor, (f) Pipe:
0.02985
Pipe Line DP/100 ft.
1.308
Friction Factor at Full Turbulence (¦t):
0.018
Straight Pipe, ft:
31.5

Fittings

Leq/D1
Leq2, 3
K1, 2 = ¦t (L/D)
Quantity
Total Leq
Total K
90o Long Radius Elbow
20
5.1
0.36
2
10.23
0.72
Branch Tee
60
15.3
1.08
1
15.34
1.08
Swing Check Valve
50
12.8
0.9
1
12.78
0.9
Plug Valve
18
4.6
0.324
1
4.6
0.324
3” x 1” Reducer4
None5
822.685
57.92
1
822.68
57.92

TOTAL

865.633
60.944
Notes:
  1. K values and Leq/D are obtained from reference 1.
  2. K values and Leq are given in terms of the larger sized pipe.
  3. Leq is calculated using Equation 5 above.
  4. The reducer is really an expansion; the pump discharge nozzle is 1” (Schedule 80) but the connecting pipe is 3”. In piping terms, there are no expanders, just reducers. It is standard to specify the reducer with the larger size shown first. The K value for the expansion is calculated as a gradual enlargement with a 30o angle.
  5. There is no L/D associated with an expansion or contraction. The equivalent length must be back calculated from the K value using Equation 5 above.
Typical Equivalent Length Method
K Value Method
Straight Pipe DP, psi
Not applicable
0.412
Total Pipe Equivalent Length DP, psi
11.734
Not Applicable
Valves and Fittings DP, psi
Not applicable
6.828
Total Pipe DP, psi
11.734
7.24
The line pressure drop is greater by about 4.5 psi (about 62%) using the typical equivalent length method (adding straight pipe length to the equivalent length of the fittings and valves and using the pipe line fiction factor in Equation 1).
One can argue that if the fluid is water or a hydrocarbon, the pipeline friction factor would be closer to the friction factor at full turbulence and the error would not be so great, if at all significant; and they would be correct. However hydraulic calculations, like all calculations, should be done in a correct and consistent manner. If the engineer gets into the habit of performing hydraulic calculations using fundamentally incorrect equations, he takes the risk of falling into the trap when confronted by a pumping situation as shown above.
Another point to consider is how the engineer treats a reducer when using the typical equivalent length method. As we saw above, the equivalent length of the reducer had to be back-calculated using equation 5. To do this, we had to use ¦t and K. Why not use these for the rest of the fittings and apply the calculation correctly in the first place?

Final Thoughts - K Values

The 1976 edition of the Crane Technical Paper No. 410 first discussed and used the two-friction factor method for calculating the total pressure drop in a piping system (¦ for straight pipe and ¦t for valves and fittings). Since then, Hooper2 suggested a 2-K method for calculating the pressure loss contribution for valves and fittings. His argument was that the equivalent length in pipe diameters (L/D) and K was indeed a function of Reynolds Number (at flow rates less than that obtained at fully developed turbulent flow) and the exact geometries of smaller valves and fittings. K for a given valve or fitting is a combination of two Ks, one being the K found in CRANE Technical Paper No. 410, designated KY, and the other being defined as the K of the valve or fitting at a Reynolds Number equal to 1, designated K1. The two are related by the following equation:
K = K1 / NRE + KY (1 + 1/D)
The term (1+1/D) takes into account scaling between different sizes within a given valve or fitting group. Values for K1 can be found in the reference article2 and pressure drop is then calculated using Equation 7. For flow in the fully turbulent zone and larger size valves and fittings, K becomes consistent with that given in CRANE.
Darby3 expanded on the 2-K method. He suggests adding a third K term to the mix. Darby states that the 2-K method does not accurately represent the effect of scaling the sizes of valves and fittings. The reader is encouraged to get a copy of this article.
The use of the 2-K method has been around since 1981 and does not appear to have “caught” on as of yet. Some newer commercial computer programs allow for the use of the 2-K method, but most engineers inclined to use the K method instead of the Equivalent Length method still use the procedures given in CRANE. The latest 3-K method comes from data reported in the recent CCPS Guidlines4 and appears to be destined to become the new standard; we shall see.
Conclusion
Consistency, accuracy and correctness should be what the Process Design Engineer strives for. We all add our “fat” or safety factors to theoretical calculations to account for real-world situations. It would be comforting to know that the “fat” was added to a basis using sound and fundamentally correct methods for calculations.

NOMENCLATURE

D
=
Diameter, ft
d
=
Diameter, inches
¦
=
Darcy friction factor
¦t
=
Darcy friction factor in the zone of complete turbulence
g
=
Acceleration of gravity, ft/sec2
hL
=
Head loss in feet
K
=
Resistance coefficient or velocity head loss
K1
=
K for the fitting at NRE = 1
KY
=
K value from CRANE
L
=
Straight pipe length, ft
Leq
=
Equivalent length of valve or fitting, ft
NRE
=
Reynolds Number
DP
=
Pressure drop, psi
n
=
Velocity, ft/sec
W
=
Flow Rate, lb/hr
r
=
Density, lb/ft3
REFERENCES
  1. Crane Co., “Flow of Fluids through Valves, Fittings and Pipe”, Crane Technical Paper No. 410, New York, 1991.
  2. Hooper, W. B., The Two-K Method Predicts Head Losses in Pipe Fittings, Chem. Eng., p. 97-100, August 24, 1981.
  3. Darby, R., Correlate Pressure Drops through Fittings, Chem. Eng., p. 101-104, July, 1999.
  4. AIChE Center for Chemical Process Safety, “Guidelines for Pressure Relief and Effluent Handling systems”, pp. 265-268, New York, 1998.
http://www.cheresources.com

1 comments:

Unknown mengatakan...

Very important blog provide very useful information for us...
Valves Dalby Qld

Posting Komentar

 
Copyright © Chemical Engineer. Design by Best Website Design
Buy Traffic and Templates On Sales